Availability: 6 in stock
SENSORWORX power pack controllers transform incoming line voltage power to Class 2 low voltage as needed by sensors or other control devices. Additionally, they switch on/off power to the connected lighting load as directed by the sensors and controls. SENSORWORX power packs utilize a powerful microprocessor to optimize its switching timing in order to ensure long relay life even when controlling high-inrush LEDs and ballast loads. As with all SENSORWORX products, these power packs are easy to install and incorporate features which reduce contractor labor time. An elongated chase nipple with snaps for quick installation and an optional snap-on low voltage wire chamber make for a hassle free contractor experience. All SENSORWORX products are proudly made in the USA.
An input signal indicating occupancy from one or more connected sensors will signal the pack’s integrated relay to close. Once closed, line voltage will flow through the relay and turn on the connected lighting load. When the input signal indicates the occupied period has ended, the relay will open and lighting will switch off. This pack is also available with an auxiliary switch input to enable manual on, hold on, and hold off configurations. Partial off (e.g. auto off to 50%) and partial on (e.g., auto on to 50%) operation can also be achieved using the optional 0-10V stepped dimming output.
FEATURES
Powers Low Voltage Sensors
Switches Line Voltage Loads
Electronically Timed Switching Ensures Long Relay Life
Integrated Test/Programming Button
Plenum Rated (UL 2043)
Optional Snap-On Attachment Provides Chamber for Low Voltage Wire Connections
Optional Switch Input for Manual On, Hold On, or Hold Off Operation
Optional 0-10V Stepped Dimming Ouput for Partial Off or Partial On Operation
SPECIFICATIONS
Operating Voltage: 120/277 VAC
Class 2 Output Ratings: 18 VDC, 150 mA (SWX-900-AX / SWX-920 only) Connected device power: 80 mA
DC Load Ratings: 20A @ 28 VDC (MAX)|1A @ 5 VDC (MIN)
Dimming Load: (Models with -D2 option only) 50mA, (0-10 VDC ballasts or drivers compliant with IEC 60929 Annex E.2)
Operating Temp: 32°F to 122°F (0°C to 50°C) Std. -40° F/C (with -HE Option)
Relative Humidity: 0-95% Non-Condensing, Indoor Use Only
Mounting: 1/2″ Knockout